6–44 Programming
Masks
[Decel Mask]
This parameter controls which adapters can select [Decel
Time 1] and [Decel Time 2]
Parameter Number 99
Parameter Type Read and Write
Factory Default 01111111
Units
Display Drive
“0” 0 Deny Control
“1” 1 Permit Control
[Fault Mask]
This parameter controls which adapters can reset a fault.
Parameter Number 100
Parameter Type Read and Write
Factory Default 01111111
Units
Display Drive
“0” 0 Deny Control
“1” 1 Permit Control
[MOP Mask]
This parameter controls which adapters can issue MOP
commands to the drive.
Parameter Number 101
Parameter Type Read and Write
Factory Default 01111111
Units
Display Drive
“0” 0 Deny Control
“1” 1 Permit Control
[Traverse Mask]
Controls which SCANport adapters are permitted to
enable the traverse function.
Parameter Number 305
Parameter Type Read and Write
Factory Default 01111111
Units
Display Drive
“0” 0 Deny Control
“1” 1 Permit Control
[Sync Mask]
Controls which SCANport adapters are permitted to
enable the sync function.
Parameter Number 308
Parameter Type Read and Write
Factory Default 01111111
Units
Display Drive
“0” 0 Deny Control
“1” 1 Permit Control
[Logic Mask]
Determines which adapters can control the drive. If the bit
for an adapter is set to “0,” the adapter will have no control
functions except for stop. In addition, the adapter can be
removed from the drive while power is applied without
causing a serial fault.
Parameter Number 92
Parameter Type Read and Write
Factory Default 01111111
Units
Display Drive
“0” 0 Deny Control
“1” 1 Permit Control
[Local Mask]
This parameter controls which adapters are allowed to take
exclusive control of drive logic commands (except stop).
Exclusive “local” control can only be taken while the drive
is stopped.
Parameter Number 93
Parameter Type Read and Write
Factory Default 01111111
Units
Display Drive
“0” 0 Deny Control
“1” 1 Permit Control