User Manual - Firmware 1.xxx-6.xxx Instruction Manual
6–34 Programming
Faults
[Fault Frequency]
This parameter stores and displays the last
[Output Freq] prior to a fault.
Parameter Number 145
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq.
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[Fault Status 1]
This parameter stores and displays the
last [Drive Status 1] prior to a fault.
Bits 0-7 are displayed on lower half of
line 2 on HIM display, while, bits 8-15 are
displayed on the upper half of line 2.
A Status description (bit ENUM) is dis-
played on line 1 (except Series A HIMs
below version 3.0).
Parameter Number 146
Parameter Type Read Only
[Fault Status 2]
This parameter stores and displays the last [Drive
Status 2] prior to a fault.
Bits 0-7 are displayed on lower half of line 2 on HIM
display, while, bits 8-15 are displayed on the upper
half of line 2.
A Status description (bit ENUM) is displayed on line
1 (except Series A HIMs below version 3.0).
Parameter Number 286
Parameter Type Read Only
[Fault Alarms 1]
This parameter stores and displays the
last alarm conditions present prior to a
fault. Refer to Chapter 7 for further alarm
information.
A Status description (bit ENUM) is
displayed on line 1 (except Series A
HIMs below version 3.0).
Parameter Number 173
Parameter Type Read Only
Enabled
Running
Command Direction
Actual Direction
Accelerating
Decelerating
Faulted
At Speed
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Alarm
0 = Reverse
1 = Forward
0 = Reverse
1 = Forward
Reference
ID
Local
Adapter ID
Reference 15 14 13 12
Freq Select 1 0 0 0 0
Preset Freq 1 0 0 0 1
Preset Freq 2 0 0 1 0
Preset Freq 3 0 0 1 1
Preset Freq 4 0 1 0 0
Preset Freq 5 0 1 0 1
Preset Freq 6 0 1 1 0
Preset Freq 7 0 1 1 1
Freq Select 2 1 0 0 0
Adapter 1 1 0 0 1
Adapter 2 1 0 1 0
Adapter 3 1 0 1 1
Adapter 4 1 1 0 0
Adapter 5 1 1 0 1
Adapter 6 1 1 1 0
Jog Frequency 1 1 1 1
Local 11 10 9
TB3 0 0 0
1001
2010
3011
4100
5101
6110
Unused 1 1 1
Bit 14
At Freq
At Current
At Torque
Current Lmt
Mtr Overload
Line Loss
Drive Ready
Forward Run
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Drive Power
Bit 14
Reverse Run
Braking
Auto Reset
Economize
At Temp
PI Max Error
Startup
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor StalledGround Warning
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mtr Overload
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Motor OL Trip
Auto Reset
Phase Loss
Heatsink Temp
Auxiliary Input
4-20 mA Loss