User Manual - Firmware 1.xxx-6.xxx Instruction Manual

Programming 6–31
Analog I/O
[Anlg Out 0 Sel]
[Anlg Out 1 Sel]
This parameter selects the source value that will drive the
analog output. This output is intended for metering only
and should not be used as process control feedback.
Parameter Number 25, 274
Parameter Type Read and Write
Factory Default “Frequency” Out 0
“Current” Out 1
Units
Display Drive Range
Frequency 0 Zero to programmed [Maximum Freq]
“Current” 1 Zero to 200% of Drive Rated
“Torque” 2 Zero to 200% of Drive Rated
“Power” 3 Zero to 200% of Drive Rated
“Voltage” 4 Zero to 200% of Drive Rated
“% Motor OL 5 Zero to 200% of Drive Rated
“% Drive OL 6 Zero to 200% of Drive Rated
“Encoder” 7 See [Encoder Freq]
“Speed Error” 8 See [Speed Error]
“PI Reference” 9 See [PI Reference]
“PI Feedback” 10 See [PI Feedback]
“PI Error” 11 See [PI Error]
“PI Output” 12 See [PI Output]
[Anlg Out 0 Offset]
[Anlg Out 1 Offset]
This parameter enables the voltage or current offset for the
analog output. This internal value offsets 0-20mA to 4-
20mA and 0-10V to 2-10V.
Parameter Number 154, 278
Parameter Type Read and Write
Factory Default “Disabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
[Anlg Out 0 Abs]
[Anlg Out 1 Abs]
This parameter selects whether a signed value or absolute
value is used for analog out.
Parameter Number 233, 277
Parameter Type Read and Write
Factory Default “Enabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
[Anlg Out 0 Lo]
[Anlg Out 1 Lo]
Sets the percentage of voltage or current output that rep-
resents the low end of the “Range” listed in [Anlg Out Sel].
Parameter Number 234, 275
Parameter Type Read and Write
Display Units / Drive Units 0.1% / 4096 = 100%
Factory Default 0.0%
Minimum Value 300.0 %
Maximum Value +300.0 %
[Anlg Out 0 Hi]
[Anlg Out 1 Hi]
Sets the percentage of voltage or current output that rep-
resents the high end of the “Range” listed in [Anlg Out
Sel].Example: To get 150% of current to equal 10V/20mA,
set this parameter to 150%.
Parameter Number 235, 276
Parameter Type Read and Write
Display Units / Drive Units 0.1% / 4096 = 100%
Factory Default 100.0 %
Minimum Value 300.0 %
Maximum Value +300.0 %
[Slot A Option]
[Slot B Option]
Displays the catalog number of the analog I/O option board
currently installed in slots A and/or B.
Parameter Number 252, 253
Parameter Type Read Only
Factory Default “Standard”
Units
Display Drive
“Standard” 0
“LA1” 1
“LA2” 2
“LA3” 3
“LA4” 4
“LA5” 5
“LA6” 6
“LA7” 7
“Undefined” 8 Board not recognized