Frequency Set
[Pulse In Scale]
Provides a scaling factor for the pulse input.
Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336-MOD-N1 option outputs 64 Hz/Hz. At full analog
reference, the pulse input to the drive will be 60 Hz x 64
Hz/Hz = 3840 pulses/sec.
Parameter Number 264
Parameter Type Read and Write
Display Units / Drive Units Factor / Pulses per Rev
Factory Default 64 PPR
Minimum Value 1
Maximum Value 4096
[Encoder PPR]
This parameter sets the scaling for encoder feedback
speed regulation. Enter the actual encoder pulses per
revolution
Parameter Number 46
Parameter Type Read and Write
Display Units / Drive Units Factor / Pulses per Rev
Factory Default 1024 PPR
Minimum Value 1
Maximum Value 4096
Scale
Factor
Incoming Pulse Rate (Hz)
Desired Command Freq.
=
Scale Factor =
3840 Hz
60 Hz
= 64