User Manual V 1-4.XX User guide

Table Of Contents
E-4 CE Conformity
Mechanical Conguration Filter Mounting
1 Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with
equivalent attenuation. Shielding/armor must be bonded to the metal bottom plate. See requirements 5 & 6 on page E-1.
2 Refer to the Filter Selection table on page E-2 for frame references and corresponding catalog numbers.
1336 IMPACT
Frames A1 - A4
1336 IMPACT
Frames B & C
To Motor
Cable Supplied with Filter
Conduit
To Motor
Three-Phase Input
Access
Panel
Flat Washer
Star Washers
Bolt
Bolt
Important: Drive and filter must be
mounted to a common back plane
with a positive electrical bond and
in close proximity to one another.
Important: A positive electrical bond must
be maintained between drive and filter at
all 4 corners. Star washers can be
eliminated if a positive electrical
bond is assured.
Three-Phase
Input
1
1
1
1
1
2
2
1