User Manual V 1-4.XX User guide

Table Of Contents
11-70 Parameters
217
Fstart Speed
1
Use Fstart Speed to set the start point at which the speed search
begins. This parameter is only active when operating in Fstart
Select mode 2 (Speed Param).
To maximize reconnect performance, always set the Fstart
Speed slightly greater than the expected reconnect motor speed.
1 Fstart Speed was added in Version 3.xx.
Parameter number 217
File:group Application: Flying Start
Parameter type linkable destination
Display x.x RPM
Factory default + base motor speed rpm
Minimum value Rev Speed Limit (Param 40)
Maximum value Forward Speed Limit (Param 41)
Conversion +4096 = base motor speed
Refer to Chapter 9, Applications, for more information.
218 Reserved
Leave this parameter set to 0.
Parameter number 218
File:group
Parameter type
Display
Factory default
Minimum value
Maximum value
Conversion
219
PwrUp Flt Status
1
PwrUp Flt Status indicates that a fault condition has been
detected during power up or reset of the drive. When a bit is 1,
the condition is true; otherwise, the condition is false.
1 PwrUp Flt Status was added in Version 3.xx.
Parameter number 219
File:group Monitor: Fault Status
Parameter type source
Display Bits
Factory default 0000 0000 0000 0000
Minimum value 0000 0000 0000 0000
Maximum value 1111 1111 1111 1111
Conversion 1 = 1
Bit Condition
0 CP EPROM
1 CP Int RAM
2 CP Ext RAM
3 CP Stack Ram
4 CP MBI
5 Reserved
Bit Condition
6 Reserved
7 Reserved
8 VP EPROM
9 VP Int Ram
10 VP Ext Ram
11 VP Stack RAM
Bit Condition
12 VP MBI
13 Reserved
14 EE Checksum
15 EE R/W
220
Ncfg Flt Status
1
Ncfg Flt Status indicates that a fault condition in the drive
CANNOT be congured as a warning. When a bit is 1, the
condition is true; otherwise, the condition is false. Bits 0 3 are
detected by hardware. Bits 4 15 are detected are detected by
software.
1 Ncfg Flt Status was added in Version 3.xx.
Parameter number 220
File:group Monitor: Fault Status
Parameter type source
Display Bits
Factory default 0000 0000 0000 0000
Minimum value 0000 0000 0000 0000
Maximum value 1111 1111 1111 1111
Conversion 1 = 1
Bit Condition
0 Bus Overvolt
1 Trans Desat
2 Ground Flt
3 IOC
4 VP Handshake
5 Diff SW Ver
Bit Condition
6 Dr Type Dif
7 III Drv Type
8 CP Handshake
9 Abs overspd
10 +/- 15v Tol
11 Auto/Diag
Bit Condition
12 Inv Temp Trp
13 Task Overrun
14 Ill Interrupt
15 Mode Timeout