User Manual V 1-4.XX User guide

Table Of Contents
2-4 Mounting and Wiring Your 1336 IMPACT Drive
Table 2.B
Maximum Motor Cable Length Restrictions 500V 600V Drives
3
All Cable Lengths Given in meters (feet)
.
NR = Not Recommended
Drive
Frame
Drive kW (hp)
Motor kW
(hp)
No External Devices w/1204-TFB2 Terminator w/1204-TFA1 Terminator
Reactor at Drive
1
Motor w/Insulation V
P-P
Motor w/Insulation V
P-P
Motor w/Insulation V
P-P
Motor w/Insulation V
P-P
1000V 1200V
1600V
2
1000V 1200V
1600V
2
1000V 1200V
1600V
2
1000V 1200V
1600V
2
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
A4
0.75 (1)
0.75 (1) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
Not
Recommended
0.37 (0.5) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2)
1.5 (2) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.2 (1.5) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
2.2 (3)
2.2 (3) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
3.7 (5)
3.7 (5) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
2.2 (3) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5) NR NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
B
5.5 15
(7.5 20)
5.5 15
(7.5 20)
NR
9.1
(30)
15.2
(50)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
30.5
(100)
91.4
(300)
182.9
(600)
C
18.5 45
(25 60)
18.5 45
(25 60)
NR
9.1
(30)
12.2
(40)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
30.5
(100)
91.4
(300)
182.9
(600)
D
56 93
(75 125)
56 93
(75 125)
NR
9.1
(30)
33.5
(110)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
61.0
(200)
91.4
(300)
182.9
(600)
E
112 224
(150 X300)
112 224
(150 X300)
NR
9.1
(30)
21.3
(70)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
F
224 336
(300 450)
224 336
(300 450)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
G
224 448
(300 600)
224 448
(300 600)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
H
522 597
(700 800)
522 597
(700 800)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
1 A 3% reactor reduces motor and cable stress but may cause a degradation of motor waveform quality. Reactors must have a turn-turn insulation rating of 2100
volts or higher.
2 1329R only
3 Values shown are for nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply
values by 0.85 for high line conditions.