User Manual

533Programming
[Input Status]
This parameter displays the on/off status of inputs
1-8 at TB3 if an optional interface card is installed.
With a Series A (version 3.0) or Series B HIM, a
Status description (bit ENUM) is displayed on line 1.
Parameter Number 55
Parameter Type Read Only
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Input 1 TB3-19
Input 2 TB3-20
Input 4 TB3-23
Input 3 TB3-22
Input 5 TB3-24
Input 6 TB3-26
Input 8 TB3-28
Input 7 TB3-27
[Freq Source]
This parameter displays the frequency source
currently commanding the drive.
Parameter Number 62
Parameter Type Read Only
Factory Default None
Units Display Drive
Adapter 1 6
Adapter 2 7
Adapter 3 8
Adapter 4 9
Adapter 5 10
Adapter 6 11
Preset 1-7 12-18
Iso Analog 19
Jog Sel 20
Use Last 0
Remote Pot 1
0-10 Volt 2
4-20 mA 3
Pulse Ref 4
Unused 5
[Freq Command]
This parameter displays the frequency that the drive
is commanded to output. This command may come
from any one of the frequency sources selected by
[Freq Select 1] or [Freq Select 2].
Parameter Number 65
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq Forward
Factory Default None
Minimum Value 400.00 Hz
Maximum Value + 400.00 Hz
[Drive Direction]
This parameter displays the commanded running
direction.
Parameter Number 69
Parameter Type Read Only
Factory Default None
Units Display Drive
Forward 0
Reverse 1
[Stop Mode Used]
This parameter displays the active stop mode.
Parameter Number 26
Parameter Type Read Only
Factory Default None
Units Display Drive
Coast 0
DC Brake 1
Ramp 2
Diagnostics