5–32 Programming
This group of parameters contains values that can be helpful in explaining the operation of
the drive. Drive status, direction, control and alarm conditions as well as drive ratings are
included.
Diagnostics
[Drive Status]
This parameter displays the actual
operating condition in binary format.
Bits 0-7 are displayed on lower half
of line 2 on HIM display, while, bits
8-15 are displayed on the upper half
of line 2.
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number 59
Parameter Type Read Only
Enabled
Running
Command Direction
Actual Direction
Accelerating
Decelerating
Faulted
At Speed
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Alarm
0 = Reverse
1 = Forward
0 = Reverse
1 = Forward
Reference
ID
Local
Adapter ID
Reference 15 14 13 12
Freq Select 1 0 0 0 0
Preset Freq 1 0 0 0 1
Preset Freq 2 0 0 1 0
Preset Freq 3 0 0 1 1
Preset Freq 4 0 1 0 0
Preset Freq 5 0 1 0 1
Preset Freq 6 0 1 1 0
Preset Freq 7 0 1 1 1
Freq Select 2 1 0 0 0
Adapter 1 1 0 0 1
Adapter 2 1 0 1 0
Adapter 3 1 0 1 1
Adapter 4 1 1 0 0
Adapter 5 1 1 0 1
Adapter 6 1 1 1 0
Jog Frequency 1 1 1 1
Local 11 10 9
TB3 0 0 0
1001
2010
3011
4100
5101
6110
Unused 1 1 1
Bit 14
[Drive Alarm]
This parameter displays which
alarm condition is present when bit
6 of [Drive Status] is high
(set to 1). Refer to Chapter 6 for
further alarm information.
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number 60
Parameter Type Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor StalledGround Warning
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Unused
Unused
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
Overcurrent
[Latched Alarms]
This parameter “stores” the [Drive
Alarm] indications (see above). Bits
will remain set (high/1), even if the
alarm condition no longer exists.
The bit(s) must be programmed to
zero to release the stored
indications.
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number 205
Parameter Type Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor StalledGround Warning
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Unused
Unused
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
Overcurrent