User Manual

530 Programming
[Flt Driv Status]
This parameter stores and displays
the last [Drive Status] prior to a
fault.
Bits 0-7 are displayed on lower half
of line 2 on HIM display, while, bits
8-15 are displayed on the upper half
of line 2.
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number 146
Parameter Type Read Only
Enabled
Running
Command Direction
Actual Direction
Accelerating
Decelerating
Faulted
At Speed
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Alarm
0 = Reverse
1 = Forward
0 = Reverse
1 = Forward
Reference
ID
Local
Adapter ID
Reference 15 14 13 12
Freq Select 1 0 0 0 0
Preset Freq 1 0 0 0 1
Preset Freq 2 0 0 1 0
Preset Freq 3 0 0 1 1
Preset Freq 4 0 1 0 0
Preset Freq 5 0 1 0 1
Preset Freq 6 0 1 1 0
Preset Freq 7 0 1 1 1
Freq Select 2 1 0 0 0
Adapter 1 1 0 0 1
Adapter 2 1 0 1 0
Adapter 3 1 0 1 1
Adapter 4 1 1 0 0
Adapter 5 1 1 0 1
Adapter 6 1 1 1 0
Jog Frequency 1 1 1 1
Local 11 10 9
TB3 0 0 0
1001
2010
3011
4100
5101
6110
Unused 1 1 1
Bit 14
[Fault Alarms]
This parameter stores and displays
the last alarm conditions present
prior to a fault. Refer to Chapter 6
for further alarm information.
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number 173
Parameter Type Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor StalledGround Warning
Bit 15 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Overcurrent
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Unused
Unused
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
[Flt Clear Mode]
This parameter controls the method for clearing
faults.
Parameter Number 39
Parameter Type Read and Write
Factory Default Enabled
Units Display Drive
Disabled 0
Faults cleared only by cycling power
Enabled 1 Faults cleared by issuing a valid
stop command or cycling power
[Ground Warning]
Enables the Ground Warning fault when the drive
senses ground current in excess of 2 amperes
(approximate). Refer to Chapter 6 for further
information.
Parameter Number 204
Parameter Type Read and Write
Factory Default Disabled
Units Display Drive
Disabled 0
No Fault Generated
Enabled 1 Ground Warning Generated
Faults