User Manual

529Programming
[Flt Motor Mode]
This parameter displays the motor mode active at
the time of the last fault.
Parameter Number 143
Parameter Type Read Only
Factory Default None
Units Display Drive
1 1
Power up sequence in progress
2 2 Motor connected, drive off
3 3 DC boost being applied
4 4 Motor running at [Dwell Frequency]
5 5 Motor accelerating
6 6 Motor at command speed
7 7 Motor decelerating
8 8 Motor coasting
9 9 Motor under DC braking
10 10 Waiting for fault reset returns to 0
11 11 Start mode
12 12 Flying start search enable
13 13 Flying start w/encoder in process
[Flt Power Mode]
This parameter displays the power mode active at
the time of the last fault. These values can be
helpful in troubleshooting for a condition causing a
fault.
Parameter Number 144
Parameter Type Read Only
Factory Default None
Units Display Drive
1 1
Power up sequence in progress
2 2 Precharge in progress
3 3 Bus voltage being stored in memory
4 4 Ready for run cmnd. after power up
5 5 Power stage diagnostics running
6 6 Line loss detection occurred
7 7 Ready for run command after stop
8 8 Drive running
9 9 Motor flux decay delay
10 10 DC braking in progress
11 11 Drive fault occurred
12 12 Flying start search enabled
13 13 Deceleration in progress
14 14 SCR wake mode
15 15 SCR check mode
16 16 SCR wait mode
[Fault Frequency]
This parameter stores and displays the last
[Output Freq] prior to a fault.
Parameter Number 145
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq.
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
Faults