This group of parameters contains the programming options for digital and analog drive
outputs.
Output Config
[Digital Out Sel]
This parameter sets the condition that closes the
output contact at TB2 terminals 10 & 11.
Parameter Number 158
Parameter Type Read and Write
Factory Default At Speed
Units Display Drive
At Speed 0
At Frequency 1
Requires value in [Dig Out Freq]
At Current 2 Requires value in [Dig Out Curr]
At Torque 3 Requires value in [Dig Out Torque]
[Dig Out Freq]
This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to At Frequency. The contact will be closed when
above this value.
Parameter Number 159
Parameter Type Read and Write
Display Units / Drive Units 0.01 Hertz / 32767 = Max Freq
Factory Default 0.00 Hz
Minimum Value 0.00 Hz
Maximum Value Programmed [Maximum Freq]
[Dig Out Current]
This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to At Current. The contact will be closed when
above this value.
Parameter Number 160
Parameter Type Read and Write
Display Units / Drive Units 0% / 4096 = 100% of Drive Rated Amps
Factory Default 0 %
Minimum Value 0 %
Maximum Value 200 %
[Dig Out Torque]
This value sets the trip point for the output contact at
TB2 terminals 10 & 11 when [Digital Out Sel] is set
to At Torque. The contact will be closed when
above this value.
Parameter Number 161
Parameter Type Read and Write
Display Units / Drive Units 0.1 Amps / 4096 = Rated Torque Amps
Factory Default 0.0 Amps
Minimum Value 0.0 Amps
Maximum Value 200% of [Rated Amps]
[Analog Out Sel]
This parameter selects the source that will drive the
analog output.
Parameter Number 25
Parameter Type Read and Write
Factory Default Frequency
Units Display Drive
Frequency 0
Zero to programmed [Maximum Freq]
Current 1 Zero to 200%
Torque 2 Zero to 200%
Power 3 Zero to 200% kW
Encoder 4 Zero to [Pulse/Enc Hertz]
Speed Adder 5 Zero to [Speed Adder}
[Anlg Out Offset]
This parameter enables the voltage or current offset
for the analog output TB2 terminals 4 & 9. This
internal value offsets 0-20mA to 4-20mA and
0-10V to 2-10V.
Parameter Number 154
Parameter Type Read and Write
Factory Default Disabled
Units Display Drive
Disabled 0
Enabled 1