User Manual

523Programming
[FStart Reverse]
This value sets the frequency at which the reverse
speed search begins. If this value exceeds
[Maximum Freq], speed search will begin at
[Maximum Freq]. Reverse search ends at zero Hertz
or when motor speed is found.
Parameter Number 157
Parameter Type Read and Write
Display Units / Drive Units 1 Hertz / Hertz
Factory Default 0 Hz
Minimum Value 0 Hz
Maximum Value 400 Hz
[Traverse Inc]
This value sets the traverse increase time
independently. See figure below.
Parameter Number 78
Parameter Type Read and Write
Display Units / Drive Units 0.01 Sec / Seconds x 100
Factory Default 0.00 Sec
Minimum Value 0.00 Sec
Maximum Value 30.00 Sec
[Traverse Dec]
This value sets the traverse decrease time
independently. See figure below.
Parameter Number 172
Parameter Type Read and Write
Display Units / Drive Units 0.01 Sec / Seconds x 100
Factory Default 0.00 Sec
Minimum Value 0.00 Sec
Maximum Value 30.00 Sec
[Max Traverse]
This value sets the peak amplitude of speed
modulation.
Parameter Number 79
Parameter Type Read and Write
Display Units / Drive Units 0.01 Hertz / 32767 = [Maximum Freq]
Factory Default 0.00 Hz
Minimum Value 0.00 Hz
Maximum Value 50% of [Maximum Freq]
Seconds
Hertz
Maximum Traverse ()
Traverse
P-Jump
P-Jump (+)
P-Jump ()
Output
Reference
Traverse Period
20
0
10 20 30 40 50 60
20
40
Maximum Traverse (+)
Traverse Function
Feature Select