User Manual

518 Programming
This group of parameters contains internally stored frequency settings.
Frequency Set
[Freq Select 1]
This parameter controls which of the frequency
sources is currently supplying the
[Freq Command] to the drive unless
[Freq Select 2] or [Preset Freq 1-7] is selected.
Refer to the Speed Select Input Table in Chapter 2.
Parameter Number 5
Parameter Type Read and Write
Factory Default Adapter 1
Units Display Drive
Adapter 1 6
Adapter 2 7
Adapter 3 8
Adapter 4 9
Adapter 5 10
Adapter 6 11
Preset 1-7 12-18
Iso Analog 19
Jog Sel 20
Use Last 0
Remote Pot 1
0-10 Volt 2
4-20 mA 3
Pulse Ref 4
Refer to [Pulse/Enc Scale] Scale Value
Unused 5 If selected, causes a Hertz Sel Fault
[Freq Select 2]
This parameter controls which of the frequency
sources is currently supplying the
[Freq Command] to the drive unless
[Freq Select 2] or [Preset Freq 1-7] is selected.
Refer to the Speed Select Input Table in Chapter 2.
Parameter Number 6
Parameter Type Read and Write
Factory Default Preset 1
Units Display Drive
Adapter 1 6
Adapter 2 7
Adapter 3 8
Adapter 4 9
Adapter 5 10
Adapter 6 11
Preset 1-7 12-18
Iso Analog 19
Jog Sel 20
Use Last 0
Remote Pot 1
0-10 Volt 2
4-20 mA 3
Pulse Ref 4
Refer to [Pulse/Enc Scale] Scale Value
Unused 5 If selected, causes a Hertz Sel Fault
[Jog Frequency]
This parameter sets the frequency the drive will
output when it receives a valid jog command.
Parameter Number 24
Parameter Type Read and Write
Display Units / Drive Units 0.1 Hertz / Hertz x 100
Factory Default 10.0 Hz
Minimum Value 0.0 Hz
Maximum Value 400.0 Hz
[Preset Freq 1-7]
These values set the frequencies that the drive will
output when selected. Refer to Speed Select Input
table in Chapter 2.
Parameter Number(s) 27-29 & 73-76
Parameter Type Read and Write
Display Units / Drive Units 0.1 Hertz / Hertz x 100
Factory Default 0.0 Hz
Minimum Value 0.0 Hz
Maximum Value 400.0 Hz