User Manual
5–9Programming
[Decel Time 1]
This value determines the time it will take the drive
to ramp from [Maximum Freq] to 0 Hz. The rate
determined by this value and [Maximum Freq] is
linear unless [S Curve Enable] is “Enabled.” It
applies to any decrease in command frequency
unless [Decel Time 2] is selected.
Parameter Number 8
Parameter Type Read and Write
Display Units / Drive Units 0.1 Second / Seconds x 10
Factory Default 10.0 Sec
Minimum Value 0.0 Sec
Maximum Value 6000.0 Sec
[Base Frequency]
This value should be set to the motor nameplate
rated frequency.
Parameter Number 17
Parameter Type Read and Write
Display Units / Drive Units 0.1 Hertz / Hertz x 10
Factory Default 60.0 Hz
Minimum Value 25.0 Hz
Maximum Value 400.0 Hz
[Base Voltage]
This value should be set to the motor nameplate
rated voltage.
Parameter Number 18
Parameter Type Read and Write
Display Units / Drive Units 1 Volt / 4096 = Drive Rtd Volts
Factory Default Drive Rated Volts
Minimum Value 25% of Drive Rated Voltage
Maximum Value 120% of Drive Rated Voltage
[Maximum Voltage]
This parameter sets the highest voltage the drive will
output.
Parameter Number 20
Parameter Type Read and Write
Display Units / Drive Units 1 Volt / 4096 = Drive Rtd Volts
Factory Default Drive Rated Volts
Minimum Value 25% of Drive Rated Voltage
Maximum Value 120% of Drive Rated Voltage
[Minimum Freq]
This parameter sets the lowest frequency the drive
will output.
Parameter Number 16
Parameter Type Read and Write
Display Units / Drive Units 0.1 Hertz / Hertz x 10
Factory Default 0.0 Hz
Minimum Value 0.0 Hz
Maximum Value 120.0 Hz
[Maximum Freq]
This parameter sets the highest frequency the drive
will output.
This parameter cannot be changed while the drive is
running.
Parameter Number 19
Parameter Type Read and Write
Display Units / Drive Units 0.1 Hertz / Hertz x 10
Factory Default 60.0 Hz
Minimum Value 25.0 Hz
Maximum Value 400.0 Hz
Standard Volts-per-Hertz Pattern
Voltage
0
0
Frequency
Motor Rated
Base Voltage
Base Frequency
Maximum Voltage
Maximum Frequency
Motor Rated
Setup