User Manual
5–7Programming
[Flux Current]
This parameter displays the amount of current that
is out of phase with the fundamental voltage
component. It is the current required to maintain
motor flux.
Parameter Number 163
Parameter Type Read Only
Display Units / Drive Units 0.1 Amp / 4096 = Rated Amps (Motoring)
Factory Default None
Minimum Value –200% Drive Rating
Maximum Value +200% Drive Rating
[% Output Power]
This parameter displays the % output power of the
drive.
Parameter Number 3
Parameter Type Read Only
Display Units / Drive Units 1 % / ±4096 = ±100%
Factory Default None
Minimum Value –200% Drive Rated Output Power
Maximum Value +200% Drive Rated Output Power
[% Output Curr]
This parameter displays the % output current of the
drive.
Parameter Number 2
Parameter Type Read Only
Display Units / Drive Units 1 % / 4096 = 100%
Factory Default None
Minimum Value 0%
Maximum Value 200% Rated Drive Output Current
Metering