User Manual

56 Programming
[4-20 mA Hertz]
This parameter displays the frequency command
present at analog current input terminals 4 & 6 of
TB2. This value is displayed whether or not this is
the active frequency command.
Parameter Number 140
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[0-10 Volt Hertz]
This parameter displays the frequency command
present at analog voltage input terminals 4 & 5 of
TB2. This value is displayed whether or not this is
the active frequency command.
Parameter Number 139
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[Pot Hertz]
This parameter displays the frequency command
present at remote pot terminals 1, 2 & 3 of TB2. This
value is displayed whether or not this is the active
frequency command.
Parameter Number 138
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[Pulse/Enc Hertz]
This parameter displays the frequency command
present at pulse input terminals 7 & 8 of TB2 or at
the encoder input terminals on TB3 (if present). This
value is displayed whether or not this is the active
frequency command.
Parameter Number 63
Parameter Type Read Only
Display Units / Drive Units 0.01 Hertz / 32767 = Maximum Freq
Factory Default None
Minimum Value 0.00 Hz
Maximum Value 400.00 Hz
[Heatsink Temp]
This parameter displays the heatsink temperature.
Parameter Number 70
Parameter Type Read Only
Display Units / Drive Units 1° C / Deg. C
Factory Default None
Minimum Value 0
Maximum Value 255° C
[Last Fault]
This parameter displays the last drive fault. It is
updated whenever a new fault occurs.
Parameter Number 4
Parameter Type Read Only
Display Units / Drive Units Fault Number / Fault Number
Factory Default None
Minimum Value None
Maximum Value None
[Torque Current]
This parameter displays the amount of current that
is in phase with the fundamental voltage component.
It is the current that is actually producing torque.
Parameter Number 162
Parameter Type Read Only
Display Units / Drive Units 0.1 Amp / 4096 = Rated Amps (Motoring)
Factory Default None
Minimum Value 200% Drive Rating
Maximum Value +200% Drive Rating
Metering