User Manual

537Programming
This group of parameters contains binary masks for all control functions. The masks control
which adapters can issue control commands.
Masks
TB3
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Each mask contains a bit for each adapter.
Individual bits can be set to Zero to lockout
control by an adapter or set to 1 to permit an
adapter to have control.
With a Series A (version 3.0) or Series B HIM,
a Status description (bit ENUM) is displayed
on line 1.
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Mask
Not Used
[Direction Mask]
This parameter controls which adapters can issue
forward/reverse commands.
Parameter Number 94
Parameter Type Read and Write
Factory Default 01111110
Units Display Drive
0 0
Deny Control
1 1 Permit Control
[Start Mask]
This parameter controls which adapters can issue
start commands.
Parameter Number 95
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
0 0
Deny Control
1 1 Permit Control
[Jog Mask]
This parameter controls which adapters can issue
jog commands.
Parameter Number 96
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
0 0
Deny Control
1 1 Permit Control
[Reference Mask]
This parameter controls which adapters can select
an alternate reference; [Frequency Sel 1],
[Frequency Sel 2] or preset speeds.
Parameter Number 97
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
0 0
Deny Control
1 1 Permit Control
[Accel Mask]
This parameter controls which adapters can select
[Accel Time 1] and [Accel Time 2].
Parameter Number 98
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
0 0
Deny Control
1 1 Permit Control
[Decel Mask]
This parameter controls which adapters can select
[Decel Time 1] and [Decel Time 2]
Parameter Number 99
Parameter Type Read and Write
Factory Default 01111111
Units Display Drive
0 0
Deny Control
1 1 Permit Control