User Manual

534 Programming
[Motor Mode]
This parameter displays the motor mode.
Parameter Number 141
Parameter Type Read Only
Factory Default None
Units Display Drive
1 1
Power up sequence in progress
2 2 Motor connected, drive off
3 3 DC boost being applied
4 4 Motor running at [Dwell Frequency]
5 5 Motor accelerating
6 6 Motor at command speed
7 7 Motor decelerating
8 8 Motor coasting
9 9 Motor under DC braking
10 10 Waiting for fault reset returns to 0
11 11 Start mode
12 12 Flying start search enable
13 13 Flying start w/encoder in process
[Power Mode]
This parameter displays the power mode.
Parameter Number 142
Parameter Type Read Only
Factory Default None
Units Display Drive
1 1
Power up sequence in progress
2 2 Precharge in progress
3 3 Bus voltage being stored in memory
4 4 Ready for run command after
power up
5 5 Power stage diagnostics running
6 6 Line loss detection occurred
7 7 Ready for run command after stop
8 8 Drive running
9 9 Motor flux decay delay
10 10 DC braking in progress
11 11 Drive fault occurred
12 12 Flying start search enabled
13 13 Deceleration in progress
14 14 SCR wake mode
15 15 SCR check mode
16 16 SCR wait mode
[Output Pulses]
This parameter displays the number of output cycles
for the PWM waveform. The count rolls over at
65535.
Parameter Number 67
Parameter Type Read Only
Display Units / Drive Units 1 Pulse / Pulses
Factory Default None
Minimum Value 0
Maximum Value 65535
[Current Angle]
This parameter displays the angle, in degrees, of
displacement between output voltage and output
current. The cosine of this number is an
approximation of output power factor.
Parameter Number 72
Parameter Type Read Only
Display Units / Drive Units 1 Deg / 255 = 360 Deg
Factory Default None
Diagnostics