User Manual

Specifications
Chapter 4
4-3
B003B200 Input Power Voltage: 380-460V AC ±10%.
Frequency: 48 to 62 Hz.
Phase: 3-phase.
AC Input Overvoltage Trip: 570V AC.
AC Input Undervoltage Trip: 275V AC.
Bus Overvoltage Trip: 810V DC for drive ratings B003-B200.
Bus Undervoltage Trip: 388V DC for Base Driver/Power Supply
Board.
Firmware Versions 1.11-3.01.
456V DC for Base Driver/Power Supply
Board.
Firmware Version 1.01.
Line Transient Protection: Line transients up to 5,000 volts peak, 320
Joules.
Logic Power Ride-Thru: 2 seconds or Longer.
–– subject to the integrity of user supplied
external circuits.
Control Logic Noise: Showering arc transients from 350 to 2,000
Immunity volts peak.
C003C200 Input Power Voltage: 500-575V AC ±10%.
Frequency: 48 to 62 Hz.
Phase: 3-phase.
AC Input Overvoltage Trip: 690V AC.
AC Input Undervoltage Trip: 343V AC.
Bus Overvoltage Trip: 975V DC.
Bus Undervoltage Trip: 485V DC.
Line Transient Protection: Line transients up to 5,000 volts peak, 320
Joules.
Logic Power Ride-Thru: 2 seconds or Longer.
–– subject to the integrity of user supplied
external circuits.
Control Logic Noise: Showering arc transients from 350 to 2,000
Immunity volts peak.