User Manual
Operation and Programming
Chapter 5
5-45
Output Meter Settings Parameter 55 -- Frequency Output (Amps)
Units = % of Maximum Output Signal
Range = 075/125
Factory Setting = 100
This parameter is used to calibrate an output frequency ammeter while the
drive is running. It may be set from 75-125% of the maximum output
signal, 1 mA. The 1 mA signal is selected by setting switch SW1 on the
Control Board to the 1 mA position.
Parameter 56 -- Frequency Output (Volts)
Units = % of Maximum Output Signal
Range = 075/125
Factory Setting = 100
This parameter is used to calibrate an output frequency voltmeter while the
drive is running. It may be set from 75-125% of the maximum output
signal, 10V DC. The 10V DC signal is selected by setting switch SW1 on
the Control Board to the 10V DC position.
Monitoring Mode Settings Parameter 57 -- Monitor Display Select
Units = Code
Range = 0/1/2
Factory
Setting
=0
This parameter sets one of three alternate monitoring modes that may be
selected while the drive is running.
When set to 0,
A0 –– monitor equivalent drive output current.
When set to 1,
A1 –– monitor equivalent motor RPM.
When set to 2,
A2 –– monitor drive control frequency.
Parameter 58 -- Motor Pole Select
Units = Code
Range = 2/4/6/8/10
Factory
Setting
=4
To allow motor RPM to be calculated and displayed when monitoring
mode
A1 is selected, this parameter is used to enter the number of motor
poles.