User Manual

Operation and Programming
Chapter 5
5-41
Lower and Upper Important: The maximum allowable drive output frequency will be
Frequency Clamp Settings determined by the lowest value programmed into the following parameters:
Parameter 3 Frequency Range
Parameter 15 Maximum Frequency
Parameter 51 Upper Frequency Clamp
Parameter 53 Bias Frequency –– If Parameter 53 is Higher Than
Parameter 54
Parameter 54 Gain Frequency –– If Parameter 54 is Higher Than
Parameter 53
Parameter 50 -- Lower Frequency Clamp
Units = Hertz
Range = 00.50/400.0
Factory
Setting
= 00.50
This parameter sets the minimum frequency or speed that the drive can be
set to by any input control signal.
From 00.50-100.0 Hz, Parameter 50 sets the Lower Frequency Clamp in
.01 Hz increments.
From 100.0-400.0 Hz, Parameter 50 sets the Lower Frequency Clamp in
0.1 Hz increments.
Important: If an external potentiometer, a 0-5V DC, a 0-10V DC or a
4-20mA frequency reference is required:
For directly proportional applications, enable Parameter 52 and enter a
minimum value of 00.50 for Parameter 53 if the Lower Frequency
Clamp is to set the minimum frequency.
For inverse follower applications, enable Parameter 52 and enter a
minimum value of 00.50 for Parameter 54 if the Lower Frequency
Clamp is to set the minimum frequency.