User Manual
Operation and Programming
Chapter 5
5-32
Preset Frequency Settings Auxiliary Preset Frequencies are enabled or disabled by Parameters 19 and
20. Individual Preset Frequency settings are selected by setting switches
S1, S2 and/or S3 as shown in Parameters 19 and 20.
Parameter 29 -- Preset Frequency 2
Units = Hertz
Range = 00.50/400.0
Factory
Setting
= 20.00
From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 2
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 2
in 0.1 Hz increments.
Parameter 30 -- Preset Frequency 3
Units = Hertz
Range = 00.50/400.0
Factory
Setting
= 30.00
From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 3
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 3
in 0.1 Hz increments.
Parameter 31 -- Preset Frequency 4
Units = Hertz
Range = 00.50/400.0
Factory
Setting
= 40.00
From 00.50-100.0 Hz, this parameter sets the value of Preset Frequency 4
in .01 Hz increments.
From 100.0-400.0 Hz, this parameter sets the value of Preset Frequency 4
in 0.1 Hz increments.