User Manual
Operation and Programming
Chapter 5
5-27
As shown in Figure 4-5 in Chapter 4 ––
If
Parameter 19 = 2 and Parameter 20 = 1
When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to
The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Preset Frequency 2 + Accel Time 2 + Decel T
ime 2
8SP OFF ON OFF Preset Frequency 3 + Accel Time 3 + Decel T
ime 3
8SP ON ON OFF Preset Frequency 4 + Accel Time 4 + Decel T
ime 4
8SP OFF OFF ON
Remote Fault Reset
8SP ON OFF ON Preset Frequency 2 + Accel Time 2 + Decel T
ime 2 + Remote Fault Reset
8SP OFF ON ON Preset Frequency 3 + Accel Time 3 + Decel T
ime 3 + Remote Fault Reset
8SP ON ON ON Preset Frequency 4 + Accel Time 4 + Decel T
ime 4 + Remote Fault Reset
If
Parameter 19 = 1 and Parameter 20 = 1
When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to
The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Accel Time 2 + Decel T
ime 2
8SP OFF ON OFF Accel Time 3 + Decel T
ime 3
8SP ON ON OFF Accel Time 4 + Decel T
ime 4
8SP OFF OFF ON
Remote Fault Reset
8SP ON OFF ON Accel Time 2 + Decel T
ime 2 + Remote Fault Reset
8SP OFF ON ON Accel Time 3 + Decel T
ime 3 + Remote Fault Reset
8SP ON ON ON Accel Time 4 + Decel T
ime 4 + Remote Fault Reset
If Parameter 19 = 0 and Parameter 20 = 1
When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Preset Frequency 2
8SP OFF ON OFF Preset Frequency 3
8SP ON ON OFF Preset Frequency 4
8SP OFF OFF ON Remote Fault Reset
8SP ON OFF ON Preset Frequency 2 + Remote Fault Reset
8SP OFF ON ON Preset Frequency 3 + Remote Fault Reset
8SP ON ON ON Preset Frequency 4 + Remote Fault Reset