If
Parameter 19 = 2 and Parameter 20 = 0
When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to
The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Preset Frequency 2 + Accel Time 2 + Decel T
ime 2
8SP OFF ON OFF Preset Frequency 3 + Accel Time 3 + Decel T
ime 3
8SP ON ON OFF Preset Frequency 4 + Accel Time 4 + Decel T
ime 4
8SP OFF OFF ON Preset Frequency 5 + Accel Time 1 + Decel T
ime 1
8SP ON OFF ON Preset Frequency 6 + Accel Time 1 + Decel T
ime 1
8SP OFF ON ON Preset Frequency 7 + Accel Time 1 + Decel T
ime 1
8SP ON ON ON Preset Frequency 8 + Accel Time 1 + Decel T
ime 1
If
Parameter 19 = 1 and Parameter 20 = 0
When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to
The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF Accel Time 2 + Decel T
ime 2
8SP OFF ON OFF Accel Time 3 + Decel T
ime 3
8SP ON ON OFF Accel Time 4 + Decel T
ime 4
8SP OFF OFF ON Accel Time 1 + Decel T
ime 1
8SP ON OFF ON Accel Time 1 + Decel T
ime 1
8SP OFF ON ON Accel Time 1 + Decel T
ime 1
8SP ON ON ON Accel Time 1 + Decel T
ime 1
If
Parameter 19 = 0 and Parameter 20 = 0
When and and and
Control Board External External External
Switch SW2 Switch S1 Switch S2 Switch S3
is Set to is Set to is Set to is Set to
The Parameters Selected are
8SP OFF OFF OFF None
8SP ON OFF OFF
Preset Frequency 2
8SP OFF ON OFF
Preset Frequency 3
8SP ON ON OFF
Preset Frequency 4
8SP OFF OFF ON
Preset Frequency 5
8SP ON OFF ON
Preset Frequency 6
8SP OFF ON ON
Preset Frequency 7
8SP ON ON ON
Preset Frequency 8