Overload Protection Settings
0
115% of Parameter 7
% of Current
Parameter 6 = 1
0 25 Hz 50 Hz 60 Hz
140% of Rated Drive Output Current
Hz
Maximum Frequency
0
% of Current
Parameter 6 = 2
115% of Parameter 7
0 25 Hz 50 Hz 60 Hz
140% of Rated Drive Output Current
Hz
Maximum Frequency
69% of Parameter 7
104% of Parameter 7
96% of Rated Drive Output Current
84% of Rated Drive Output Current
0
% of Current
Parameter 6 = 3
115% of Parameter 7
0 15 Hz 50 Hz 60 Hz
140% of Rated Drive Output Current
Hz
Maximum Frequency
69% of Parameter 7
84% of Rated Drive Output Current
Overload Protection
Overload
Protection
Overload
Protection
Parameter 07 -- Overload Current
Units = Amps
Range = 000.1/500.0
Factory Setting = None
Parameters 6 and 7 will work in conjunction if Parameter 7 matches the
rated amps located on the motor nameplate, and Parameter 6 is set to 1, 2
or 3. When Parameter 6 is set to 0, the setting of Parameter 7 will have no
effect on drive operation. The overload current value for Parameter 7 may
be set in 0.1A increments.