User Manual

Installation and Wiring
Chapter 4
4-15
If You Use
200/208/230V AC, 1Phase Input Voltage
Power Recommended
Rating Wire Wire Recommended
Code Group Size Torque
ZAA 2 14 AWG (2.5mm
2
) 9 In-lbs (1.02N-m)
AAA 2 14 AWG (2.5mm
2
) 9 In-lbs (1.02N-m)
YAA 2 14 AWG (2.5mm
2
) 9 In-lbs (1.02N-m)
BAA 2 12 AWG (4.0mm
2
) 9 In-lbs (1.02N-m)
CAA 2 10 AWG (6.0mm
2
) 9 In-lbs (1.02N-m)
DAA 2 8 AWG (10.0mm
2
) 10 In-lbs (1.13N-m)
EAA 2 8 AWG (10.0mm
2
) 10 In-lbs (1.13N-m)
W
ire group number chart, page 4-6.
CAUTION
:
230/208VA.C.
Input Voltage Only
Use 75 Degree C AWG Copper Wire
Torque to Lb-in
(Power Terminal Block Cover)
Select
from the following drive input fuses.
Drive Rating ZAA
Fuse Size 15AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating AAA
Fuse Size 15AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating Y
AA Fuse Size 15AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating BAA
Fuse Size 30AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating CAA
Fuse Size 40AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating DAA
Fuse Size 70AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating EAA
Fuse Size 80AFuse T
ype 600V Class K5 UL Listed or Equivalent