User Manual

Installation and Wiring
Chapter 4
4-11
If You Use
200/208/230V AC, 3Phase Input Voltage
Power Recommended
Rating Wire Wire Recommended
Code Group Size Torque
ZAA 2
14 A
WG (2.5mm
2
)
9 Inlbs (1.02Nm)
AAA 2
14 A
WG (2.5mm
2
)
9 Inlbs (1.02Nm)
YAA 2
14 A
WG (2.5mm
2
)
9 Inlbs (1.02Nm)
BAA 2
12 A
WG (4.0mm
2
)
9 Inlbs (1.02Nm)
CAA 2
10 A
WG (6.0mm
2
)
9 Inlbs (1.02Nm)
DAA 2
8 A
WG (10.0mm
2
)
10 Inlbs (1.13Nm)
EAA 2
8 A
WG (10.0mm
2
)
10 Inlbs (1.13Nm)
Wire group number chart, page 46.
CAUTION :
230/208VA.C.
Input Voltage Only
Use 75 Degree C AWG Copper Wire
Torque to Lb-in
(Power Terminal Block Cover)
Select
from the following drive input fuses.
Drive Rating ZAA
Fuse Size 15AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating AAA
Fuse Size 15AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating Y
AA Fuse Size 15AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating BAA
Fuse Size 30AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating CAA
Fuse Size 40AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating DAA
Fuse Size 70AFuse T
ype 600V Class K5 UL Listed or Equivalent
Drive Rating EAA
Fuse Size 80AFuse T
ype 600V Class K5 UL Listed or Equivalent
If You Use
380/415/460V AC, 3Phase Input Voltage
Power Recommended
Rating Wire Wire Recommended
Code Group Size Torque
AAB 2 14 AWG (2.5mm
2
) 9 In-lbs (1.02N-m)
YAB 2 14 AWG (2.5mm
2
) 9 In-lbs (1.02N-m)
BAB 2 14 AWG (2.5mm
2
) 9 In-lbs (1.02N-m)
CAB 2 14 AWG (2.5mm
2
) 9 In-lbs (1.02N-m)
W
ire group number chart, page 4-6.
CAUTION :
460/415/380VA.C.
Input Voltage Only
Use 75 Degree C AWG Copper Wire
Torque to Lb-in
(Power T
erminal Block Cover)
Select
fr
om the following drive input fuses.
Drive Rating AABFuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating YABFuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating BABFuse Size 15AFuse Type 600V Class K5 UL Listed or Equivalent
Drive Rating CABFuse Size 20AFuse Type 600V Class K5 UL Listed or Equivalent