User Manual
Specifications
Chapter 3
3-3
Load Requirements A balanced 3-phase inductive motor load is typical. Other motor loads may
require application assistance.
Output Power Waveform: Sine coded pulse width modulated waveform.
Specifications
Voltage: Drive Rating ZAA-GAA
0 to applied input voltage, 200V AC,
208V AC,
or 230V AC –– maximum output voltage
cannot exceed applied input voltage.
Drive Rating AAB-CAB
0 to applied input voltage, 380V AC, 415V
AC,
or 460V AC –– maximum output voltage
cannot exceed applied input voltage.
Frequency Programmable Min and Max Limits
Range: 0 to 400 Hz remote frequency command.
0.5 to 400 Hz local frequency command.
Frequency ± 0.5% of selected maximum output frequency
Regulation: –10 to +50°C ambient temperature range.
Accel/Decel: Four independently programmable accel times.
Four independently programmable decel times.
Each time may be programmed over a range
from 0.1 to 1600 seconds. If 0 is entered, the
drive will default to 40 ms.
Accel Stall Protection: 140% of rated current.
Decel Stall Protection: 380V DC for 230V AC drive input voltage.
760V DC for 460V AC drive input voltage.
Volts-per-Hertz: Selectable constant or square v/Hz curves.
DC Boost: 0-40% of maximum output voltage
adjustable in 1% increments.