User Manual
Factory and Field Parameter Settings
Appendix C
C-2
Factory and Field Parameter Settings -- Parameters 0128
Function Parameter Parameter Factory Field
Group Number Name Units Range Setting Setting
Accel
and Decel
0I
ACCEL TIME 1
Seconds 0000/1600 005.0
Settings
02
DECEL TIME 1
Seconds 0000/1600 005.0
VoltsperHertz Curve
03
FREQUENCY RANGE
Code 50/60/FF 60
Settings
04 VOLTSPERHERTZ CURVE Code 0/1 0
DC Boost Setting
05 DC BOOST SELECT % of Output Voltage 00/40 00
Overload Protection
06 MOT
OR DUTY
Code 0/1/2/3 2
Settings
07
OVERLOAD CURRENT
Amps 000.1/500.0 ❶
Local/Remote Control Enable
08
LOCAL/REMOTE CONTROL
Code 0/1/2/3 0
Local/Remote Speed Enable
09
LOCAL/REMOTE FREQUENCY
Code 0/1/2/3 0
Reverse Enable
I0
REVERSE LOCKOUT
Off/On 0/1 0
Stop Setting
II STOP SELECT Code
0/1
0
DC Brake
I2
DC HOLD FREQUENCY
Hertz 00.50/60.00 00.50
Settings
I3
DC HOLD TIME
Seconds 000/10.0 000
I4
DC HOLD VOL
TS Code 0/10 0
Max Speed
I5
MAXIMUM FREQUENCY
Hertz 50.00/400.0 60.00
Settings
I6
BASE FREQUENCY
Hertz 50.00/250.0 60.00
Accel and Decel Hold
I7
ACCEL FREQUENCY HOLD
Off/On 0/1 1
Enable
I8
DECEL FREQUENCY HOLD
Off/On 0/1 1
Preset Frequency and
I9
FREQUENCY SELECT
Code 0/1/2 0
Aux Accel/Decel Enable
20 TB15 PRESET/RESET Code 0/1 0
Aux Interlock Enable
2I AUXILIAR
Y INTERLOCK
Code 0/1 0
Drive Supplied Contact
22
CR1 SELECT
Code 1/2/3 1
Settings
23
CR2 SELECT
Code 0/1/2/3 0
24
CR1 FREQUENCY
Hertz 00.50/400.0 00.50
25
CR2 FREQUENCY
Hertz 00.50/400.0 00.50
Jog
26 JOG FREQUENCY Hertz 00.50/20.00 10.00
Settings
27 JOG ACCEL TIME Seconds 0000/1600 005.0
28 JOG DECEL TIME Seconds 0000/1600 005.0
❶
Factory setting is determined by the output current rating shown on the drive nameplate.