User Manual
Preventive Maintenance and
Troubleshooting Common Drive Problems
Appendix B
B-13
5. The drive will not ramptostop -- No fault is displayed.
Is
Parameter 1
1 Stop Select set to ramptostop?
Set Parameter 1
1 to 0.
Yes
Does Parameter 59 show an OU fault stored?
Yes
The drive is tripping on overvoltage during decel. Refer to page B3.
No
No
Is
the DC Hold Frequency set to high -- Is parameter 12 set to 00.50 Hz?
No
Set Parameter 12 to 00.50 Hz.
Yes
Is Parameter 18 Decel Frequency Hold on -- Does the motor have an
overhauling load?
Yes
No
If
Parameter 18 Decel Frequency Hold is set to 1 (On), an overhauling load
may
cause the decel ramp to hold at one frequency for an extended period.
This
may cause ramptostop commands to appear to be nonfunctional.
Contact your nearest AB representative for application assistance.