Technical Specifications
1329I-5.0 Integrated Drive/Motor — January, 1999
Drive Protection/Fault Detection
Output overcurrent:
Trip level = 200% of max peak rated current
Output ground fault:
Trip level = 200% of max peak rated current
DC bus overvoltage:
Motor thermal overload:
Trip time = 1 minute at 150% of rated current (CT)
Trip time = 1 minute at 110% of rated current (VT)
DC bus undervoltage:
Line Voltage Trip Level
460 VAC 830 VDC
230 VAC 415 VDC
115 VAC 208 VDC
Line Voltage Trip Level
460 VAC 435 VDC
380 VAC 358 VDC
230 VAC 218 VDC
115 VAC 109 VDC