Manual

Parameters B-5
44 0x0F-44-1 Stop Select
Stopping mode used by the drive when a stop is initiated.
0 = Coast to stop
1 = Ramp to stop
Get/Set 0 to 1 0
45 0x0F-45-1 Reverse Disable
Disables reverse rotation of the motor.
0 = Reverse enabled
1 = Reverse disabled
Get/
Set
(2)
0 to 1 0
46 0x0F-46-1 IR Compensation
Compensation for the voltage drop across the stator resistance in an induction motor. A
voltage is added to the commanded output voltage based on the load current. The default
value of 100% is the factory determined optimum for the drive. It can be adjusted higher or
lower to suit the needs of the application. A setting of 0% disables this function.
Get/Set 0% to
150%
100%
47 0x0F-47-1 Slip Compensation
Compensation for the inherent slip in an induction motor. A frequency is added to the
commanded output frequency based on load current. The default value of 100% is the factory
determined optimum for the drive. It can be adjusted higher or lower to suit the needs of the
application. A setting of 0% disables this function.
Get/Set 0.0% to
150.0%
100.0%
48 0x0F-48-1 Analog Minimum
The percent of analog input used to represent Parameter 30 - [Minimum Frequency]. If the
minimum analog input equals minimum frequency, no action is needed. If it is desired to
adjust the analog input to equal Parameter 30 - [Minimum Frequency], use Parameter 08 -
[Analog Input] to adjust the analog input to the desired level and then enter the value in
Parameter 48.
Get/
Set
(2)
0.0% to
100.0%
0%
49 0x0F-49-1 Analog Maximum
The percent of analog input used to represent Parameter 31 - [Maximum Frequency]. If the
maximum analog input equals maximum frequency, no action is needed. If it is desired to
adjust the analog input to equal Parameter 31 - [Maximum Frequency], use Parameter 08 -
[Analog Input] to adjust the analog input to the desired level and then enter the value in
Parameter 49.
Get/
Set
(2)
0.0% to
100.0%
100.0%
50 0x0F-50-1 Fault Reset
Resets the drive after a fault. This parameter is a command. It will be reset to 0 = No Action
after the command is completed.
0 = No Action
1 = Reset Fault
Get/
Set
(2)
0 to 1 0
51 0x0F-51-1 Preset Speed 1
Programmed value that sets the frequency that the drive outputs when this preset is selected.
Get/Set 0.0 Hz to
120.0 Hz
10.0 Hz
52 0x0F-52-1 Preset Speed 2
Programmed value that sets the frequency that the drive outputs when this preset is selected.
Get/Set 0.0 Hz to
120.0 Hz
20.0 Hz
53 0x0F-53-1 Preset Speed 3
Programmed value that sets the frequency that the drive outputs when this preset is selected.
Get/Set 0.0 Hz to
120.0 Hz
30.0 Hz
54 0x0F-54-1 Preset Speed 4
Programmed value that sets the frequency that the drive outputs when this preset is selected.
Get/Set 0.0 Hz to
120.0 Hz
40.0 Hz
55 0x0F-55-1 Preset Speed 5
Programmed value that sets the frequency that the drive outputs when this preset is selected.
Get/Set 0.0 Hz to
120.0 Hz
50.0 Hz
56 0x0F-56-1 Preset Speed 6
Programmed value that sets the frequency that the drive outputs when this preset is selected.
Get/Set 0.0 Hz to
120.0 Hz
60.0 Hz
57 0x0F-57-1 Preset Speed 7
Programmed value that sets the frequency that the drive outputs when this preset is selected.
Get/Set 0.0 Hz to
120.0 Hz
70.0 Hz
DeviceNet Parameters
101 0x0F-101-1 Switches MAC ID
The state of the node address DIP switches (1 – 6). This address may not reflect the present
address of the module if the baud rate DIP switches are set to 3. In this case, Parameter 103
- [NV MAC ID] is used.
Get 0 to 63 63
#
Object
Mapping
Name and Description
Access
Rule
(1)
Units/
Range
Factory
Default
(1)
Get = Read. Set = Write. Set access is allowed only if DIP switch 10 on the 1329I Integrated drive/motor is set to On (Figure 2.3).
(2)
The parameter can be set only when the drive is stopped.
(3)
The parameter can be set only when the 1329 Integrated drive/motor does not have an active I/O connection.