Manual

4-4 Configuring a Scanner
Figure 4.6 Scan List Editor Dialog Box
8. Click the new node to highlight it, and then click Edit I/O Parameters.
The Edit Device I/O Parameters dialog box appears.
Figure 4.7 Edit Device I/O Parameters Dialog Box
9. Set up the scanner for Polled I/O, Change of State, or Cyclic data
exchange. Refer to your settings for Parameter 108 - [Input Assembly]
and Parameter 107 - [Output Assembly] to determine your I/O sizes:
In Figure 4.7
, we show an example that uses polled I/O. We selected the
Enable box, typed 4 in the Rx box because we are using Input Assembly
71, and typed 4 in the Tx box because we are using Output Assembly 21.
Finally, we selected Every Scan in the Poll Rate box.
108 - [Input Assembly] Rx Size 107 - [Output Assembly] Tx Size
0 = No Data 0 0 = No Data 0
50 = Basic Overload 1 1 = Basic Contactor 1
51 = Extended Overload 1 2 = Two Command Contactor 1
52 = Basic Motor Control 1 3 = Basic Overload 1
53 = Extended Motor Control 1 4 = Basic Motor Control 1
54 = Extended Motor Control 2 1 5 = 2 Command Motor 1
70 = Basic Speed Control 4 20 = Basic Speed Control 4
71 = Extended Speed Control 4 21 = Extended Speed Control 4
100 = Speed Control in Hz 4
106 = Preset Control with Speed 4
8
8