Manual
Publication 1329I-5.4 – January, 2000 P/N 194395 (01)
Copyright 2000 Rockwell International Corporation. Printed in USA
Bulletin 1329I CE Filter
Option Specifications
1329I-NLF1 1329I-NLF3 1329I-JLF1 1329I-JLF3
Input Voltage 115/230 VAC 230/460 VAC 115/230 VAC 230/460 VAC
Input Phases Single Phase Three Phase Single Phase Three Phase
Frequency 50/60 Hz
Rated Current 14 Amps 9 Amps 14 Amps 9 Amps
Power Dissipation 5 Watts
Leakage Current (Worst Case) 0.5 mA
Weight 0.33 Kg (0.73 lb) 0.45 Kg (0.99 lb) 4.72 Kg (10.41 lb) 4.89 Kg (10.78 lb)
Enclosure Internal NEMA 12/IP 65
Operating Temperature 0° to 40°C (32° to 104°F)
Storage Temperature -40° to 85°C (-40° to 185°F)
Relative Humidity 5% to 95%, non-condensing
Vibration 1 G operational, 2.5 G non-operational
Shock 15 G operational, 30 G non-operational
Altitude 1000 meters (3300 feet) without derating. For every 91.4 meters (300 feet) above
1000 meters, derate current by 1%. Above 3000 meters (10,000 feet), consult your
Allen-Bradley Sales Office.
International Standards and
Approvals
U
L
®
L
I
S
T
E
D
9
6
6
X
I
N
D
C
O
N
T
E
Q
UL508C
U
L
®
L
I
S
T
E
D
9
6
6
X
I
N
D
C
O
N
T
E
Q
C
CSA 22.2
EMC Directive 89/336
LV: EN 50178, EN 60204
EMC: EN 61800-3, EN 50081-1, EN 50082-2