1329I Integrated Drive/Motor CE Filter Option Kit
Filter Wiring
4. Connect wires as shown in the diagram below. (Three Phase unit shown.)
ATTENTION:
To guard against possible equipment damage, RFI
filters can only be used with AC supplies that are nominally
balanced with respect to ground. In some installations, three-
phase supplies are occasionally connected in a 3-wire
configuration with one phase grounded (Grounded Delta). The
filter must not be used in Grounded Delta supplies.
Conduit/4-Wire Cable
Nearest Building Structure Steel
PE
1329I Integrated Drive Motor
L1
IN
L2
IN
L3
IN
W3
OUT
W2
OUT
W1
OUT
T/L3
S/L2
R/L1
CE Filter
DC+
DC-
DBR
T/L3
S/L2
R/L1
PE
L3
L2
L1
1.3 Nm
(12 in-lb)
1.3 Nm
(12 in-lb)