Reference Guide Owner manual
6 Rockwell Automation Publication 1305-5.2.2 - September 2013
1305 Adjustable Frequency AC Drive
1305 Series C Parameter List
Speed Indicator
LEDs
(only available
with digital
speed control)
Illuminates in steps to give an approximate visual indication of the commanded speed.
If the Analog Speed Potentiometer option has been ordered, the Increment/Decrement keys
and Speed Indicator LEDs will be replaced by the pot.
Item Name Description
Group/
Parameter No. Units
Min.
Value
Max.
Value
Default
Value
Group/
Parameter No. Units
Min.
Value
Max.
Value
Default
Value
Metering Analog Invert 84 Text
(1)
—— Disabled
Output Current 54 0.01 Amps 0.00 2x Drive Output Current — 4-20 mA Loss Sel 81 Text
(1)
—— Stop/Fault
Output Voltage 1 1 Volt 0 Maximum Voltage — Stop Select 10 Text
(1)
—— Ramp
Output Power 23 0.01 kW 0.00 2x Rtd. Dr. Output Power — DC Hold Time 12 0.1 Sec 0.0 150.0 0.0
DC Bus Voltage 53 1 Volt 0 410…230V Drive DC Hold Volts 13 1 Volt 0 25% of Max DRV 0
815…460V Drive — DB Enable 11 Text
(1)
—— Disabled
Output Freq. 66 0.01 Hz 0.00 Maximum Frequency — Motor Type 41 Text
(1)
— — Induc/Reluc
Freq. Command 65 0.01 Hz 0.00 +400.00 0.00 Compensation 52 Text
(1)
—— Comp
MOP Hz 42 0.01 Hz 0.00 400.00 —
Frequency Set
Drive Temp 70 1 deg. C 0 100 — Freq Select 1 5 Text
(1)
—— Adapter 1
Last Fault 4 Numeric 0 Max. Fault No. — Freq Select 2 6 Text
(1)
—— Remote Pot
% Output Power 3 1% 0 200% Drive Rated Power — Jog Frequency 24 0.1 Hz 0.0 400.0 10.0
% Output Curr. 2 1% 0 200% Rtd. Dr. Out. Curr. — Prst/2nd Accel 26 Text
(1)
—— Preset
Setup Upper Presets 72 Text
(1)
—— Disabled
Input Mode 21 Text
(1)
— — Three Wire Accel Time 2 30 0.1 sec 0.0 3600.0 5.0
Freq Select 1 5 Text
(1)
— — Adapter 1 Decel Time 2 31 0.1 sec 0.0 3600.0 5.0
Accel Time 1 7 0.1 sec 0.0 3600.0 10.0 Preset Freq 1 27 0.1 Hz 0.0 400.0 10.0
Decel Time 1 8 0.1 sec 0.0 3600.0 10.0 Preset Freq 2 28 0.1 Hz 0.0 400.0 20.0
Base Frequency 17 1 Hz 40 400 60 Preset Freq 3 29 0.1 Hz 0.0 400.0 30.0
Base Voltage 18 1 Volt 25% of DRV 100% of Max DRV Max DRV Preset Freq 4 73 0.1 Hz 0.0 400.0 40.0
Maximum Voltage 20 1 Volt 25% of DRV 110% of Max DRV Max DRV Preset Freq 5 74 0.1 Hz 0.0 400.0 50.0
Minimum Freq 16 1 Hz 0 120 0 Preset Freq 6 75 0.1 Hz 0.0 400.0 60.0
Maximum Freq 19 1 Hz 40 400 60 Preset Freq 7 76 0.1 Hz 0.0 400.0 0.0
Stop Select 10 Text
(1)
— — Ramp Skip Freq 1 32 1 Hz 0 400 400
Current Limit 36 1% 20% of DRC 150% of DRC 150% of DRC Skip Freq 2 33 1 Hz 0 400 400
Overload Mode 37 Text
(1)
— — No Derating Skip Freq 3 34 1 Hz 0 400 400
Overload Current 38 0.1 Amps 20% of DRC 115% of DRC 115% of DRC Skip Freq Band 35 1 Hz 0 15 0
Sec Curr Limit 141 1% 0% of DRC 150% of DRC 0% of DRC MOP Increment 22 1 Hz/Sec 0.00 255.00 1.00
Adaptive I Lmt 149 Text
(1)
— — Enabled Analog Filter 144 Text
(1)
— — 100%
Advanced Setup Feature Select
Minimum Freq 16 1 Hz 0 120 0 Run On Power Up 14 Text
(1)
—— Disabled
Maximum Freq 19 1 Hz 40 400 60 Reset/Run Tries 85 Numeric 0 9 0
Base Frequency 17 1 Hz 40 400 60 Reset/Run Time 15 0.1 Sec 0.5 30.0 1.0
Base Voltage 18 1 Volt 25% of DRV 100% of Max DRV Max DRV S Curve Enable 57 Text
(1)
—— Disabled
Break Frequency 49 1Hz 0 120 30 S Curve Time 56 0.1 Sec 0.0 300.0 0.0
Break Voltage 50 1 Volt 0 50% of Max DRV Dr. Size Dep. Language 47 Text
(1)
—— Approp. Lang.
Maximum Voltage 20 1 Volt 25% of DRV 110% of Max DRV Max DRV Cable Length 143 Text
(1)
—— Short
DC Boost Select 9 Text
(1)
— — Break Point Rated Slip 146 0.1 Hz 0.0 5.0 2.0
Start Boost 48 1 Volt 0 25% of Max DRV Dr. Size Dep. Slip Comp Adder 148 0.01 Hz 0.00 5.00 —
Run Boost 83 1 Volt 0 25% of Max DRV 0 IR Comp % 147 1% 0% 150% Drv. Depend.
PWM Frequency 45 0.1 kHz 2.0 8.0 4.0 (Table continued on next page.)