User Manual

Programming
5-5
This group of parameters consists of commonly viewed drive operating conditions such as drive output fre-
quency, output voltage, output current and command frequency. All parameters in this group are Read Only.
Metering
[Out
p
ut Current]
Parameter # 54 Factory Default None
[Output
Current]
Parameter Type Read Only Minimum 0.00
This parameter displays the output current present at TB1,
terminals T1, T2 & T3 (U, V & W).
Units 0.01 Amps Maximum Two Times Drive
Output Current
[Out
p
ut Volta
g
e]
Parameter # 1 Factory Default None
[Output
Voltage]
Parameter Type Read Only Minimum 0
This parameter displays the output voltage present at TB1,
terminals T1, T2 & T3 (U, V & W)
Units 1 Volt Maximum Maximum Voltage
[Out
p
ut Power]
Parameter # 23 Factory Default None
[Output
Power]
Parameter Type Read Only Minimum 0
This parameter displays the output power present at TB1,
terminals T1, T2, & T3 (U, V & W).
Units 0.01 kW Maximum Two Times Rated
Drive Output Power
[DC Bus Volta
g
e]
Parameter # 53 Factory Default None
[DC
Bus
Voltage]
Parameter Type Read Only Minimum 0
This parameter displays the DC bus voltage level. Units 1 Volt Maximum 410 - 230V Drive
815 - 460V Drive