User Manual

Programming
5-48
Masks Group (continued)
[
Start Mask
]
Parameter # 95 Factory Default 01111111
[Start
Mask]
Parameter Type Read & Write
This parameter determines which adapters can issue start
commands.
Units Byte Settings 1
0
Permit Control
Deny Control
[
Jo
g
Mask
]
Parameter # 96 Factory Default 01111111
[Jog
Mask]
Parameter Type Read & Write
This parameter determines which adapters can issue jog
commands.
Units Byte Settings 1
0
Permit Control
Deny Control
[
Reference Mask
]
Parameter # 97 Factory Default 01111111
[Reference
Mask]
Parameter Type Read & Write
This parameter determines which adapters can control the
switching between the available freq. reference sources.
Important: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control
[
Accel Mask
]
Parameter # 98 Factory Default 01111111
[Accel
Mask]
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Accel Time 1] and [Accel Time 2].
Important: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control
[
Decel Mask
]
Parameter # 99 Factory Default 01111111
[Decel
Mask]
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Decel Time 1] and [Decel Time 2].
Important: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control