Owner's manual

Chapter 5 –Programming
5-10
Set Up Group (cont.)
[
Ba
s
e
F
re
qu
en
c
y
]
Parameter # 17 Factory Default 60 Hz
[
Ba
s
e
F
re
qu
en
c
y
]
Parameter Type Read & Write Minimum 40 Hz
This value should be set to the motor nameplate Rated
Frequency.
Units 1 Hz Maximum 400 Hz
[
Ba
s
e
V
ol
t
a
g
e
]
Parameter # 18 Factory Default Max. Drive Rated Volts
[
Ba
s
e
V
ol
t
a
g
e
]
Parameter Type Read & Write Minimum 25% of Max. Drive Rated Volts
This value should be set to the motor nameplate Rated
Voltage.
Units 1 Volt Maximum 100% of Max. Drive Rated Volts
[
Max
imum V
ol
t
a
g
e
]
Parameter # 20 Factory Default Max. Drive Rated Volts
[
Max
imum V
ol
t
a
g
e
]
Parameter Type Read & Write Minimum 25% of Max. Drive Rated Voltage
This parameter sets the highest voltage the drive will
output.
Units 1 Volt Maximum 100% of Max. Drive Rated Volts
[
M
i
n
imum F
re
q]
Parameter # 16 Factory Default 0 Hz
[
M
i
n
imum F
re
q]
Parameter Type Read & Write Minimum 0 Hz
This parameter sets the lowest frequency the drive will
output. IMPORTANT: All analog inputs to the drive
(4-20mA, 0-10V, Remote Pot) are scaled for the range
[Minimum Freq] to [Maximum Freq].
Units 1 Hz Maximum 120 Hz
IMPORTANT: This parameter can not be
programmed while the drive is running.