Table B.4 Parameter Grouping/User Settings (cont.)
Group Parameter Name Parameter # Display Units Drive Units
Scale Factor
Min Max Factory Setting User’s
Setting
Run On Power Up 14 Text 1 –– –– Disabled
t
Reset/Run Tries 85 Numeric 1 0 9 0
e
lect
Reset/Run Time 15 Seconds 100 0.5 30.0 1.0
e
Se
l
S Curve Enable 57 Text 1 –– ––– Disabled
ure
S Curve Time 56 Seconds 10 0.0 300.0 0.0
eatu
Language 47 Text 1 –– –– English
F
e
Balance Freq 80 Hz 1 0 255 0
Balance Time 79 Seconds 1 0 255 0
Balance Angle 78 Numeric 1 0 255 0
Cable Length 143 Text 1 –– –– Short
t
p
Output Config 1 90 Text 1 –– –– Faulted
tput
Up
Output Config 2 91 Text 1 –– –– Running
Out
p
Set
Analog Out Sel 25 Text 1 –– –– Frequency
O
S
Above Freq Val 77 Hz 1 0 400 0
Fault Buffer 0 86 Numeric 1 –– –– ––
Fault Buffer 1 87 Numeric 1 –– –– ––
l
ts
Fault Buffer 2 88 Numeric 1 –– –– ––
ault
Fault Buffer 3 89 Numeric 1 –– –– ––
F
a
Clear Fault 51 Text 1 –– –– Ready
Cur Lim Trip En 82 Text 1 –– –– Default Run
Line Loss Fault 40 Text 1 –– –– F03 Enable
Fault Clear Mode 39 Text 1 –– –– Enabled
Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions.