Owner's manual
Appendix B –
Serial Communications
B-6
Table B.4 Parameter Grouping/User Settings (cont.)
Group Parameter Name Parameter # Display
Units
Drive Units
Scale Factor ➁
Min Max Factory Setting User‘s
Setting
Input Mode 21 Text ➀ 1 –– –– Three Wire
Freq Select 1 5 Text ➀ 1 –– –– Adapter 1
Accel Time 1 7 Seconds 10 0.0 3600.0 10.0
Decel Time 1 8 Seconds 10 0.0 3600.0 10.0
p
Base Frequency 17 Hz 1 40 400 60
Up
Base Voltage 18 Volts 1
25% of DRV
Drive Rated Volts Drive Rated Volts
S
et U
Maximum Voltage 20 Volts 1
25% of DRV
Drive Rated Volts Drive Rated Volts
S
e
Minimum Freq 16 Hz 1 0 120 0
Maximum Freq 19 Hz 1 40 400 60
Stop Select 10 Text ➀ 1 –– –– Ramp
Current Limit 36 % 1
20% of DRC
150% of Drive Rated Current (DRC) 150% of DRC
Overload Mode 37 Text ➀ 1 –– –– No Derating
Overload Current 38 Amps 100 = DRC
20% of DRC
115% of Drive Rated Current (DRC) 115% of DRC
Sec Curr Limit 141 % 1 0 150% of Drive Rated Current (DRC) 0
➀ Refer to Table B.5 on pages B-13, B-14 and B-15 for the numerical equivalent of the text descriptions. ➁ Refer to page B-2.