Owner's manual
Chapter 5 –Programming
5-48
Masks Group (cont.)
[
S
t
ar
t
Ma
sk]
Parameter # 95 Factory Default 01111111
[
S
t
ar
t
Ma
sk]
Parameter Type Read & Write
This parameter determines which adapters can issue start
commands.
Units Byte Settings 1
0
Permit Control
Deny Control
[J
o
g
Ma
sk]
Parameter # 96 Factory Default 01111111
[J
o
g
Ma
sk]
Parameter Type Read & Write
This parameter determines which adapters can issue jog
commands.
Units Byte Settings 1
0
Permit Control
Deny Control
[R
e
f
eren
c
e
Ma
sk]
Parameter # 97 Factory Default 01111111
[R
e
f
eren
c
e
Ma
sk]
Parameter Type Read & Write
This parameter determines which adapters can control the
switching between the available freq. reference sources.
IMPORTANT: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control
[
A
cc
el
Ma
sk]
Parameter # 98 Factory Default 01111111
[
A
cc
el
Ma
sk]
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Accel Time 1] and [Accel Time 2].
IMPORTANT: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control
[D
e
c
el
Ma
sk]
Parameter # 99 Factory Default 01111111
[D
e
c
el
Ma
sk]
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Decel Time 1] and [Decel Time 2].
IMPORTANT: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control