Owner's manual
Chapter 5 –Programming
5-38
Output Configuration Group (cont.)
[
Analo
g
O
ut
Sel
]
Parameter # 25 Factory Default “Frequency”
[
Analo
g
O
ut
Sel
]
Parameter Type Read & Write
This parameter selects the value to which the 0-10V DC
upu T sprpr
Units None Setting ‘‘Frequency”
0 to [Maximum Freq]
T
hi
s
p
a
r
am
e
t
er
se
l
e
ct
s
th
e
v
al
ue
to which th
e
0-10V DC
analog output at TB2-5 is proportional to.
‘‘Current”
0 to 200% of Rated Drive Output Current)
upu T sprpr
‘‘Bus Volts”
0 to Maximum Bus Voltage– 410V/230V Drives
815V/460V Drives
‘‘Power”
0 to 200% of Drive Rated OutputPower
“Output Volts”
0 to Drive Rated Voltage
[
A
b
o
v
e
F
re
q V
al
]
Parameter # 77 Factory Default 0 Hz
[
A
b
o
v
e
F
re
q V
al
]
Parameter Type Read & Write Minimum 0 Hz
This parameter sets the level at which Output 1 or Output 2
will transition when [Output 1 Config] or [Output 2
Config] are set to ‘‘Above Freq”. This provides an
indication that the drive is operating above the
programmed frequency value.
Units Hertz Maximum 400 Hz
NOTE: This parameter can not be programmed
while the drive is running.
[
A
b
o
v
e
Cu
rr
V
al
]
Parameter # 142 Factory Default 0 % of Drive Rated Current ➀
[
A
b
o
v
e
Cu
rr
V
al
]
Parameter Type Read & Write Minimum 0 % of Drive Rated Current ➀
This parameter sets the level at which Output 1 or Output 2
will transition when [Output 1 Config] or [Output 2
Config] are set to ‘‘Above Curr”. This provides an
indication that the drive output current exceeds the
programmed value.
Units 1% Maximum 150% of Drive Rated Current ➀
➀ The drive rated output current is based on three phase input ratings. See page 5-14 for Single Phase Input Rating instructions.