Owner's manual

Chapter 5 –Programming
5-33
Feature Select Group (cont.)
[R
e
s
e
t/Ru
n
T
im
e
]
Parameter # 15 Factory Default 1.0 Sec
[R
e
s
e
t/Ru
n
T
im
e
]
Parameter Type Read & Write Minimum 0.5 Sec
This value sets the time between restart attempts when
[Reset/Run Tries] is a value other than zero.
IMPORTANT: [Reset/Run Tries] is a cumulative count.
This counter resets to zero if four (4) minutes elapses
since the last fault.
Units 0.1 Second Maximum 30.0 Sec
[
S
Cu
r
v
e
Ena
b
le
]
Parameter # 57 Factory Default ‘‘Disabled”
[
S
Cu
r
v
e
Ena
b
le
]
Parameter Type Read & Write
This parameter enables a fixed shape S-Curve. Units None Settings ‘‘Enabled”
‘‘Disabled”
a Accel Time'
1 or 2
aDecel Time '
1 or 2
Enabled
Disabled
a 2X Accel Time 1 or 2 ' a 2X Decel Time 1 or 2 '
Figure 5.16 S-Curve
Accel/Decel times are double the active accel/decel time
settings.
IMPORTANT: The setting for [S-Curve Time] must be 0.
IMPORTANT: If [Stop Select] is set to “S Curve”
then the decel time will be double the active decel
setting when a stop command is provided.