Chapter 1 –Information and Precautions
1-6
Table 1.A Drive Rating and Derating Guidelines
Motor Rating
Voltage
an
Catalog
3 O Input 1 O Input
ol a e
Rating
Numb
IP30
HP kW
Output ➀➁
Current (A)
HP kW
Output ➀➁
Current (A)
1305-AA02A 1/2 0.37 2.3
200-230V
/6
1305-AA03A 3/4 0.55 3 1/2 0.37 2.3
22
50/60 Hz
1305-AA04A
1 0.75 4.5 3/4 0.55 3
1305-AA08A 2 1.5 8 1 0.75 4.5
1305-AA12A 3 2.2 12 2 1.5 8
1305-BA01A 1/2 0.37 1.3
380-460V
/6
1305-BA02A 3/4 0.55 1.6
86
50/60 Hz
1305-BA03A
1 0.75 2.3
Nv e
1305-BA04A 2 1.5 4
N
ot A
v
ailabl
e
1305-BA06A 3 2.2 6
1305-BA09A 5 4.0 9
In general:
When operating the drive in an ambient temperature at or near
the maximum operating temperature (50°C), the following
derating guidelines are recommended to guard against
overheating depending on application and operating conditions.
Motor Full Load Amps (FLA) should not exceed the drive output current rating.
If the [PWM Frequency] is set above 4kHz, the output current must be derated per the
chart on page 5-20.
Output current value listed for 200V input voltage. At 230V input voltage, output
current is 9.6A for 3 phase and 6.8A for single phase.
Output current value listed for 380V input voltage. At 415V input voltage, output
current is 5.3A. At 460V input voltage, output current is 4.8A.
Output current value listed for 380V input voltage. At 415V input voltage, output
current is 8.4A. At 460V input voltage, output current is 7.6A.