Owner manual

Appendix
A
A–1
Publication 1302-5.0 January, 1998
Technical Specifications
Table A.A - Service Conditions
AC Line Distribution Capacity
(Maximum)
ThreeĆphase 575ĂVAC, with 30,000Ăamps symmetrical
fault current capacity
Control Method AllĆdigital, pulseĆwidthĆmodulated (PWM)
Carrier Frequency 4ĂkHz, 6ĂkHz, or 8ĂkHz, software selectable
Displacement Power Factor 0.96
Line Frequency 50/60ĂHz (±5ĂHz)
Line Voltage Variation ć10% to +10%
Line Dip RideThrough 500Ămilliseconds
Linearity 0.05 (Speed reference to output frequency)
LongĆterm Frequency Stability 0.01%
Minimum Frequency Range 0.5 ć 30ĂHz
Maximum Frequency Range 30 ć 240ĂHz
Maximum Load 150% for 1 minute (based on Drive nameplate rating)
Motor Lead Lengths 76Ămeters (250Ăfeet) total (See table 3.7 for more
information)
Overcurrent Trip IET 200% rated Drive current
Table A.B - Dimensions
Enclosure Height Depth Width Weight
B 301.7Ămm (11.88") 160.1Ămm (6.30") 222.3Ămm (8.75") 5.4Ăkg (12 lb)
C 357.8Ămm (14.10") 158.2 mm (6.20") 278.1Ămm (10.9") 8.1Ăkg (18 lb)
Table A.C - Environmental Conditions
Operating Temperature to +ā40°C (32° to 104°F) ć enclosed Drives
to +ā55°C (32° to 131°F) ć open chassis (cover removed)
Storage Temperature ćāā40° to +65°C (ćāā40° to +149°F)
Humidity 5 to 95% (nonĆcondensing)
Altitude Do not install the Drive above 1000Ămeters (3300Ăfeet) without
derating output power. For every 91.4Ămeters (300Ăfeet) above
1000Ămeters (3300Ăfeet) up to 3033Ămeters (10,000Ăfeet),
derate the output current by 1%. Above 3033Ămeters
(10,000Ăfeet), contact your local Allen-Bradley sales office for
assistance.