Multi–Speed Preset Wiring
Multi-speed preset wiring connects to terminals 6 through 8, and 11.
See Figure 5.7. When control type 3 is selected through parameter
F-00, remote terminal strip control is enabled with multi-speed
presets. This mode of operation changes the functionality of
terminals 6 through 8 and may be used in place of 2- and 3-wire
start/stop wiring. See Figure 5.8.
When you enable multi-speed preset operation, the state of terminals
7 and 8 determine the source of the speed reference:
    
0 0 Terminal Strip Analog Input
0 1 MultiĆSpeed Preset 1 (Parameter FĆ23)
1 0 MultiĆSpeed Preset 2 (Parameter FĆ24)
1 1 MultiĆSpeed Preset 3 (Parameter FĆ25)