Specifications The following specifications are provided for the Terminator Option.
1
The drive PWM carrier frequency that you choose affects the heat dissipation and the surface temperature
of the terminator.
Heat Dissipation
This chart is based on an ambient temperature of 45 degrees C.
Category Specifications
Input power 380-600V, Three-Phase
Maximum Drive Carrier
Frequency
1
TFA1 – 6 kHz
TFB2 – 2 kHz
Refer to “Drive Programming” on page 9 for additional information.
Ambient temperature 0-40 degrees C (32-104 degrees F)
Humidity 5-95% non-condensing
Atmosphere Class 1, Division 2
Heat dissipation
1
Refer to the heat dissipation table below.
Enclosure type IP65 (NEMA Type 4x)
Hazardous
Environment Rating
T3 (200
° C); Groups A, B, C, D
Agency certification U.L., C-UL
Altitude derating Full rating 0-1000 meters (0-3280 feet)
Ambient
Temperature
Limit
Altitude
m
(ft)
40
30
35
0 4,000
(13,200)
3,000
(9,900)
2,000
(6,600)
1,000
(3,300)
degrees C.
Drive
Frequency
Length
meters (feet)
1204-TFA1 Terminator 1204-TFB2 Terminator
460 Volts + 10% 600 Volts + 10% 460 Volts + 10% 600 Volts + 10%
Watts Heatsink° Watts Heatsink° Watts Heatsink° Watts Heatsink°
6 kHz 91 (300) 210W 142° C 220W 150° C
Must Use 2 kHz
183 (600) 250W 160
° C 260W 169° C
4 kHz 91 (300) 170W 125
° C 180W 133° C
183 (600) 180W 130
° C 210W 138° C
2 kHz 91 (300) 80W 81
° C100W95° C 200W 139° C 290W 182° C
183 (600) 90W 88