User guide
5–17Block Transfer Emulation Instructions
1203–5.5 September 1995
Message Operation
Fault Queue Entry Read Full reads the contents of the fault queue
specified in word 3 of the request. The response returns the fault text
which can be ASCII text. The text will have every two characters in
reverse order. In addition, the 1336 FORCE returns a time stamp,
indicating the day and time the fault occurred.
If an error has occurred, word 2 of the response returns a negative
value.
Example
In this example, Fault Queue Entry number 3 was retrieved from a
1336 PLUS drive. The drive response returned the ASCII text Drive
Reset Flt, with each character reversed. The fault code for this
example is 22.
Data File Format
* Example only – These values vary depending on parameters and products.
# ASCII Display values
8308*
22*
r D
\00\12
\07\00
30313* 8293* 25938* 25971* 8308*
\03\00 v i l F
e
t \00\16
27718*
e R
e s t
3 1792 3*
18 1792 3* 29252*
0
N10:0
N10:90
123456789
PLC request
Drive response
N10:100
N10:90
#
N10:100
#